Filed initially with the Secretary of State on April 4, 1972,
under Act 98, P.A. 1913, these rules took effect 15 days after filing. On
January II, 1978, these rules were adopted by reference into the Administrative
Rules under Act 399, P.A. 1976, which is the Michigan Safe Drinking Water
Act.
(By authority conferred on the department of public
health by Act 399, P.A.
1976, and by sections 6, 10, of Act No. 98 of the Public Acts of 1913, as
amended, and sections 9 and 427 of Act No. 380 of the Public Acts of 1965,
as amended, being sections 325.203, 325.206, 325.210, 16.109, and 16.527
of the Compiled Laws of 1948.) R 325.11401 Definitions
Rule 1401. As used in this part:
(a) "Backflow" means water of questionable quality,
wastes, or other contaminants entering a public water supply system due to
a reversal of flow.
(b) "Cross connection means
a connection or arrangement of piping or appurtenances through which a backflow
could occur.
(c) "Safe air gap" means the
minimum distance of a water inlet or opening above the maximum high water
level or overflow rim in a fixture, device, or container to which public
water is furnished which shall be at least 2 times the inside diameter of
the water inlet pipe, but shall not be less than 1 inch and need not be more
than 12 inches.
(d) "Secondary water supply" means a water supply system maintained
in addition to a municipal type public water supply, including but not limited
to water systems from ground or surface sources not meeting the requirements
of Act No. 98 of the Public Acts of 1913, as amended, being sections 325.201
to 325.214 of the Compiled Laws of 1948, or water from a public water supply
which in any way has been treated, processed, or exposed to any possible
contaminant or stored in other than an approved storage facility.
(e) "Submerged inlet" means a water pipe or extension thereto
from a public water supply terminating in a tank, vessel, fixture, or appliance
which may contain water of questionable quality, waste, or other contaminant
and which is unprotected against backflow.
(f) "Water utility" means a governmental unit, municipal or private corporation, association, partnership, or individual engaged in furnishing water to the public for household or drinking purposes.
R 325.11402 Compliance with regulations and local
codes.
Rule 1402. A connection with a public water supply system shall comply with existing laws, ordinances and rules including:
(a) Act No. 266 of the Public Acts of 1929, as amended, being sections
338.901 to 338.917 of the Michigan Compiled Laws.
(b) Local ordinances or rules providing acceptable
protection against cross connections.
R 325.11403 Cross connections prohibited.
Rule 1403.
(1) A cross connection shall not be made between a public water supply system and a secondary water supply.
(2) A cross connection shall not be made by submerged inlet.
(3) A cross connection shall not be made between a public water supply and piping which may contain sanitary waste or a chemical contaminant.
(4) A cross connection shall not be made between
a public water supply system and piping immersed in a tank or vessel which
may contain a contaminant.
R 325.11404 Local cross connection control
programs.
Rule 1404.
(1) A water utility shall develop a comprehensive control program for the elimination and prevention of all cross connections. The plan for the program shall be submitted to the department of public health for review and approval within one year after the effective date of these rules. when the plan is approved, the water supply shall implement the program for removal of all existing cross connections and prevention of all future cross connections.
(2) The program shall include but not be limited to:
(a) A complete description of the method of administering the program, including the designation of inspection and enforcement agency or agencies. The local authority for implementation of the program shall be indicated, preferably by ordinance.
(b) A time schedule for inspection and reinspection of all water utility customers premises for possible cross connections. The periodic reinspection shall be used to ascertain whether or not safe air gaps or required protective devices are in place and in working order.
(c) A description of the methods and devices (as
approved by the department of public health) used to protect the public water
supply.
R 325.11405 Corrections and protective devices.
Rule 1405.
(1) A user of public water shall obtain written
approval by the water utility or authorized inspection agency of any proposed
corrective action or protective device before using or installing it.
(2) The total time allowed for completion of the
necessary corrections shall be contingent upon the degree of hazard involved
and include the time required to"obtain and install equipment. If the cross
connection has not been removed, after a reasonable period of time, the water
utility shall physically separate the public water supply from the on-site
piping system in such a manner that the two systems cannot again be connected
by any unauthorized person.
(3) A water utility shall report annually to the department of public health on the status of the cross connection control program on a form provided by the department.
R 325.11406 Piping identification.
Rule 1406. When a secondary water source is used in addition to a public water supply system, exposed public water and secondary water piping shall be identified by distinguishing colors or tags and so maintained that each pipe by be traced readily in its entirety. If piping is so installed that it is impossible to trace it in its entirety, it will be necessary to protect the public water supply at the service connection in a manner acceptable to the department of public health.
R 325.11407 Private water storage tanks.
Rule 1407. A private water storage tank supplied
from a public water supply system shall be deemed a secondary water supply
unless it is designed and approved for potable water usage.
The following section outlines the various devices used for
protection against cross connections. Specific installations and/or use
restrictions apply to some of these devices or methods of protection. Some
methods noted are not approved, but nevertheless have been used in the past
as a means of protection.
14.3.1 Air Gap Separation
"Safe air gap" is defined in Rule 325.11401 as, "the minimum
distance of a water inlet or opening above the maximum high water level or
overflow rim in a fixture, device, or container to which public water is
furnished which shall be at least two times the inside diameter of the water
inlet pipe, but shall not be less than one inch and need not be more than
12 inches." The illustrations on Page 10 show safe air gap arrangements for
water storage and makeup tanks.
The installation shown on Page 11 of an approved air gap at
the service line (entrance to plant system) is an acceptable solution for
protecting the public system from cross connections. Any installation
must be properly designed as no bypass will be allowed. With an air
gap, this would necessitate standby pumps and power if a continuous supply
of water is required.
Air gaps used as routine protection in homes for installations
such as sinks, bathtubs, washers, and water softeners have certainly proven
to be an effective method of protecting against backsiphonage.
However, for other users and other types of cross connections,
an air gap on the interior portion of the system is not generally accepted
as satisfactory protection. Theoretically, it is a fine solution, however,
practically speaking, air gaps on inplant problems have proven to be
unacceptable, particularly where pressure is required or where splashing
cannot be or is not tolerated. Examples of such installations would be
hospital and pathology laboratories, mortuary
tables and sinks, research (bacteriologic and/or chemical) laboratories,
plating tanks, and wash and rinse tanks.
An air gap installed on the customer's service line is theoretically the highest type of protection for the public water supply system. However, it must be properly designed to provide a constant supply of water at an acceptable pressure. A properly designed and approved air gap installed at the service line will satisfactorily protect the public water supply system from the possibility of backflow from all types of cross connections.
LARGE BUILDING WITH AIR GAP AT WATER STORAGE
TANK
AIR GAP AT MAKEUP TANK FOR A DUAL WATER
SYSTEM
'SAFE AIR GAP' - GROUND LEVEL STORAGE
TANK
14.3.2 Reduced Pressure Principle Backflow Preventers
The reduced pressure principle backflow preventer is an arrangement
of spring loaded check valves designed to prevent the backflow of water.
Page 13 illustrates a cross section of the device. Zone 1 within the schematic
diagram of the reduced pressure principle backflow preventer is maintained
at the same pressure as the public water supply system. During normal operating
conditions as shown on Page 14 the water will pass the spring loaded check
valve "A" into zone 2. The zone of highest pressure is shown as the darkest
shaded area, and the pressure decreases as the intensity of the shading
decreases. The pressure within this zone is less due to the head loss passing
through check valve "A". The water then passes through the spring loaded
check valve ~B" into zone 3 and on to the inplant system with pressure again
reduced. The spring loaded differential pressure relief valve "C~ is maintained
in a closed position due to the higher pressure in zone I than in zone 2.
The spring loaded pressure of approximately 2 psi tends to hold the relief
valve in an open position.
If the pressure within the public water
supply system becomes less than the inplant
system (Page 15), the normal direction of flow through the backflow preventer
would tend to reverse. However, check valve "B" should seat and restrict
the flow of any water back even as the higher pressure from the inplant system
would enter zone 2, but check valve "A" would restrict further movement back
toward the public water supply system.
Valve "C" at the differential pressure relief port is
normally held in a closed position since
the pressure in zone I is higher than in zone 2. The pressure differential
opposes a 2 psi residual pressure on the spring loaded relief valve. Thus,
if the water pressure in zone 2 plus the 2 psi residual spring loaded pressure
on the relief valve is greater than the pressure in zone 1, the differential
pressure relief valve. "C" opens and water is discharged through the relief
port to the atmosphere. There must be a free discharge at the drain
port and the discharge must be visible. If it is necessary to pipe any discharge
to another area, it may be accomplished by a free discharge through a visible
air gap into a collection device such as a funnel and gravity flow to discharge
at a more desirable point.
The water utility and any user contemplating the installation
of this unit must understand that it operates on the basis of a pressure
loss across each of the valves. If the user cannot obtain satisfactory service
due to the built-in head loss, problems can be anticipated if such a device
is installed.
Depending upon the design of the internal piping system, it may be possible to isolate certain critical areas with such a device; an example would be a bay of plating tanks, particularly if fed by only one service line.
REDUCED PRESSURE PRINCIPLE BACKFLOW
PREVENTER
This device when properly installed, tested, and
maintained will be acceptable for protection
of the public water system from backflow in the situations listed in Section
14.8. Since the device has a drain port between the two spring loaded check
valves, the reduced pressure principle backflow preventer must be installed
in a location not subject to flooding and also where accessible for observation.
It also must be protected from adverse weather conditions as the diaphragm
which is a part of relief valve "C" could be damaged by freezing. Care must
be taken to install these devices in accordance with manufacturers
recommendations.
Maintenance is necessary for any mechanical equipment if we
are to rely upon it maintaining its protective functions; therefore, any
mechanical protective device must be installed in a location where it is
accessible for routine inspection, testing, and required repair. These devices
are mechanical in nature and subject to breakdown, and they must be isolated
during periods of inspection and repair. If there is only one service line
from the public system and if water service is required 100% of the time,
it will be necessary to install a second reduced pressure principle backflow
preventer in parallel with proper valving in order to provide for an
uninterrupted protected supply from the public system.
The reduced pressure principle backflow preventer by itself
when properly installed and maintained will provide adequate protection for
the public water supply system from all types of cross connections that may
result in either backpressure or backsiphonage backflow. Page 17 illustrates
a typical reduced pressure principle backflow preventer.
14.3.3 Four-Way Plug Valve
When an internal plumbing system is supplied by both a secondary
water supply and a public water supply system, an effort must be made to
separate the two sources. When properly installed, the four-way plug valve
as shown on Page 18 provides air gap separation since one of
the two sources is vented to the atmosphere.
This prevents a secondary source from continually being pumped against the
public supply. The four-way plug valve should be installed in such a manner
that the line vented to the atmosphere will drain. The four-way plug valve
has considerable head loss built in, however, unlike the reduced pressure
principle backflow preventer, this head loss can be reduced by oversizing
the device. It is not satisfactory protection if the downstream piping within
the customers premise is further cross connected.
14.3.4 Four-Way Plug Valve and Reduced Pressure Principle
Backflow Preventer in Series
Page 19 illustrates the relative locations of the two pieces
of equipment when the four-way plug valve and a reduced pressure principle
backflow preventer are installed in series. This combination of protective
devices is meaningful if the entire secondary water supply and the public
water supply come together at one point only and neither source bypasses
the four-way plug valve. While the two
pieces of equipment installed in series provide the
recommended solution to these problems, it may be acceptable to utilize the
reduced pressure principle backflow preventer by itself with most secondary
water supplies. The local program should define acceptable protection for
certain situations since some communities may well require the installation
of the two devices in series.
14.3.5 Vacuum Breakers
Vacuum breakers may be acceptable for some applications, however,
they should not be solely relied on to protect the public water supply from
backsiphonage at customers such as medical laboratories, pathology laboratories,
bacteriologic, physiologic, and chemical research laboratories, hospitals,
plating industries, etc.
Vacuum breakers are effective against backsiphonage only
and shall not be used where there is any possibility that positive pressure
either from a pump, a pressure device, or from elevated piping on the discharge
side can be developed on the downstream side of the device or where it may
be subject to flooding.
Properly installed vacuum breakers will provide adequate protection
for individual toilets, urinals, high school chemistry laboratory sinks,
and lawn sprinkling systems. The vacuum breakers installed to protect against
backsiphonage on lawn sprinkling systems must be full sized (pipe size) and
must be at least 14 inches above ground level and at least 6 inches above
the highest sprinkling head (12 inches if using a pressure vacuum breaker).
On large lawn sprinkler systems and distribution lines serving them, it may
be acceptable to install two or more vacuum breakers in parallel. Paqes 21
through 24 illustrate both atmospheric and pressure type
vacuum breakers and typical applications.
he hose bibb type atmospheric
vacuum breaker shown on Pane 22 when installed on a frost proof outlet typically
will not allow drainage to occur. Consequently, the vacuum breaker must be
manually opened to prevent ice damage to the hose outlet piping.
14.3.5.1 Atmospheric Vacuum Breaker
This device allows air to enter the water supply line when
the pressure in the public system or the service line is reduced to zero
or below. It must be installed on the discharge side of the last shut-off
valve in order that the float mechanism will be operated routinely, hence
not "frozen in an open position. This device
must be installed in the high point of the water supply piping at least 6
inches above the piping outlet. An atmospheric vacuum breaker should not
be under continuous pressure for more than 12 hours.
VACUUM BREAKER CROSS-SECTION
(Shown Open to Atmosphere)
VACUUM BREAKER CROSS-SECTION
(Shown Open to Atmosphere)
TYPICAL INSTALLATIONS OF ATMOSPHERIC VACUUM BREAKERS
Sprinkler System Application
A. 14" Minimum recommended height above grade level
B. Vacuum breakers - Minimum of 6" above highest sprinkler head
C. Shut off valve must be upstream from atmospheric vacuum breakers
D. Two or more vacuum breakers in parallel may be required on large lawn sprinkler services to provide the rated flow of the service line.
Hose Bibb Application
Hose Bibb
Vacuum Breaker - Must be installed at least 6" above ground
14.3.5.2 Pressure Vacuum Breaker
This device has a vacuum relief valve which is internally loaded, normally by means of a spring. Because of this spring loading, the pressure vacuum breaker can be installed in a location where it is continuously under normal pressure; i.e., on the supply side of a shut-off valve. It must be installed in the high point of the water supply piping at least 12 inches above the piping outlet.
A. Valves may be located downstream from pessure vacuum breakers
B. This unit is not positive protection against back pressure
Test Cocks
Vacuum Breaker Cross-Section (Shown Open to
Atmosphere)
INSTALLATION OF VACUUM BREAKERS ON PROCESS TANKS
(Prohibited in some jurisdictions)
Atmospheric Vacuum Breaker - No Valves Allowed Downstream from Atmospheric Vacuum Breakers
Pressure Vacuum Breaker - Valves May Be Installed Downstream from Pressure Vacuum Breakers
NOTES:
1) Vacuum breakers should not be used in a dusty or corrosive atmosphere
2) Use hot water type vacuum breakers on hot water lines
3) If vacuum breakers are used as protection on tanks containing liquids which are hazardous to health, further protection should be required on the main service line
14.3.6 Barometric Loop
The barometric loop as shown
on Page 27 can be installed to adequately
protect the city supply from backsiphonage. The device must be properly designed,
must be installed so that it is adequately protected against freezing, and
must not be used in a position where it could possibly be subject
to backpressure. Air lift is a potential problem and a check valve should
be installed at top of loop to break any possible flow.
When properly installed, the barometric loop will protect the
public water supply system from backsiphonage. The top leg of the loop must
be a minimum of 35 feet above the spill rim of the highest free water surface,
as a perfect vacuum can lift water approximately 34 feet
14.3.7 Unapproved Methods
The following is a brief discussion of methods which are
not approved to protect against backflow.
14.3.7.1 Check valves, Double check valves
Check valves even when installed in series have not proven
to be effective protection against the hazards of backflow. These devices
will not be acceptable for providing essential health protection to the public
water supply system. They may be used to protect the public supply from aesthetic
problems such as stale water in privately owned storage tanks maintained
for fire protection. Double check valve assemblies are acceptable means of
protection for low pressure untreated boilers.
A device that is many times mistaken for a reduced pressure
zone backflow preventer but which is considered only equivalent to a double
check valve arrangement is the vented double check backflow preventer. This
device is acceptable only for low hazard applications where double checks
or double check valve assemblies are permissible. These devices are listed
in the appendix with the double check valve assemblies.
14.3.7.2 Spool connection
This type of protection against cross connections as shown
on Page 28 has in the past been used to separate the public supply. from
a secondary supply. This type of separation is not an acceptable form
of protection and should be replaced by an approved device. If an industry,
etc., wishes to maintain a spool connection, it could be allowed with a reduced
pressure principle backflow preventer installed on the public water supply
side of the spool connection. The reduced pressure principle backflow preventer
should be installed as soon as possible following the discovery
of the spool connection.
Basically, no credit for protection can be given to a spool connection and these existing units should be replaced as deemed necessary by the potential hazard involved and details of the local enforcement program.
14.3.7.3 Swing connection
The type of protection against cross connections as shown on Page 28 has in the past also been used to separate the public supply from a secondary supply. This type of device can be acceptable from a public health standpoint only if a reduced pressure principle backflow preventer is installed on the public water supply side of the connection. It should be noted that this type of device is difficult and cumbersome to use and is a detriment to its real usefulness.